| 1. |
All
units are physically identical and have a packed
shipping weight of 125 LBS. |
| 2. |
Units
are trimmed at 100 PSIG as standard . Lower trims
are available. |
| 3. |
Incoming
water line pressure must be 10 PSIG greater than
generator operating pressure. If not, a motor/pump
must be used. Specify Sussman 38002A high pressure
feedwater motor/pump system. |
| 4. |
When
ordering: Specify Model No., KW, volts/ph and motor/pump,
if required. |
| 5. |
Water
connection is 1/4 NPT. Steam outlet is 1/2 NPT. |
|
| DIMENSIONAL
INFORMATION |
|
SYMBOL |
INCHES |
|
A |
20
1/2 |
|
B |
17
1/2 |
|
C |
17
7/8 |
|
D |
15
3/4 |
|
MODEL |
KW |
VOLTS |
PH |
AMPS |
PPH |
|
MBA3 |
3 |
120,
208, 240 |
1 |
25,
15, 13 |
9 |
|
MBA6 |
6 |
208,
240, 480 |
3 |
17,
15, 8 |
18 |
|
MBA9 |
9 |
208,
240, 480 |
3 |
25,
22, 11 |
27 |
|
MBA12 |
12 |
208,
240, 480 |
3 |
34,
29, 15 |
36 |
|
MBA18 |
18 |
208,
240, 480 |
3 |
50,
44, 22 |
54 |
|
MBA20 |
20 |
208,
240, 480 |
3 |
56,
49, 25 |
60 |
| SYMBOL |
DESCRIPTION |
|
1 |
STRAINER |
|
2 |
WATER
SOLENOID |
|
3 |
CHECK
VALVE |
|
4 |
DRAIN
VALVE |
|
5 |
STEAM
OUTLET |
|
6 |
GAUGE
GLASS ASSEMBLY |
|
7 |
SAFETY
VALVE |
|
8 |
PRESSURE
GAUGE |
|
9 |
HI-LIMIT
PRESSURE CONTROL |
|
10 |
OPERATING
PRESSURE CONTROL |
|
11 |
ACCESS
PANEL |
|
12 |
ON/OFF
SWITCH |
<<Return