SSH
Electric Steam Superheater Specifications
|
The
following chart gives guidelines to properly
select a Sussman Series SSH steam superheater
for your application. Specify voltage / phase
/ hertz. Contact factory for additional sizing
guidelines
|
GAUGE
PRESSURE
(PSIG) |
REQUIRED
BTU'S PER LB. OF STEAM
TO REACH FINAL TEMPERATURE OF: |
| 300°F
|
400°F
|
450°F
|
500°F
|
600°F
|
700°F
|
| 15 |
152 |
193 |
223 |
253 |
314 |
374 |
| 25 |
144 |
206 |
236 |
266 |
327 |
387 |
| 35 |
136 |
197 |
227 |
257 |
318 |
378 |
| 45 |
131 |
192 |
222 |
252 |
313 |
373 |
| 55 |
- |
188 |
218 |
248 |
309 |
369 |
| 65 |
- |
181 |
211 |
241 |
303 |
363 |
| 75 |
- |
179 |
209 |
239 |
301 |
361 |
| 85 |
- |
176 |
206 |
236 |
297 |
357 |
| 95 |
- |
174 |
204 |
234 |
295 |
355 |
| 105 |
- |
171 |
201 |
231 |
292 |
352 |
| 115 |
- |
169 |
199 |
229 |
290 |
350 |
| 125 |
- |
168 |
198 |
228 |
289 |
349 |
| 135 |
- |
168 |
198 |
228 |
289 |
349 |
| 145 |
- |
162 |
192 |
222 |
284 |
344 |
| 155 |
- |
161 |
191 |
221 |
282 |
342 |
| 165 |
- |
160 |
190 |
220 |
281 |
341 |
| 175 |
- |
161 |
191 |
221 |
282 |
342 |
| 185 |
- |
159 |
189 |
219 |
280 |
340 |
| 195 |
- |
156 |
186 |
216 |
277 |
337 |
| 205 |
- |
159 |
189 |
219 |
280 |
340 |
| 215 |
- |
159 |
189 |
219 |
280 |
340 |
| 225 |
- |
155 |
185 |
215 |
276 |
336 |
| 235 |
- |
151 |
181 |
211 |
272 |
332 |
| 245 |
- |
149 |
179 |
209 |
270 |
330 |
| 255 |
- |
149 |
179 |
209 |
270 |
330 |
|
<<Return
to SSH Main Page>> |
|
|