Main Menu

Blowdown Separators

SEPARATES VAPORS AND LIQUIDS DURING BOILER BLOWDOWN.
 
PREVENTS LIVE STEAM FROM ESCAPING


 

Suggested Hook-Up to Boiler

 

 

Model
Number

 

 

 

Boiler Range
kW

Dimensions (inches)

 

Shpg. Wt.
Lbs.

Inlet
NPT

Outlet
NPT

 

BDT-ASME36

 

0-50

 

1"

 

2"

 

125

 

 

BDT-ASME42

 

60-250

 

1"

 

2"

 

230

 

 BDT-ASME44*

0-200

1"

 2"

300

 

BDT-ASME48

 

 

260-590

 

1 1/4"

 

2"

 

260

 

BDT-ASME54

 

 

600-1000

 

1 1/2"

 

3"

 

290

                                                                                     * Item has CRN for Canadian Market

Sussman Blowdown separators are built to ASME Section VIII. The separators accept the flash stream and effluent from the boiler blowdown and reduce the temperature and pressure to insure a safe discharge of water and sludge. Steam flash and pressure are absorbed and pass harmlessly to the outside via a vent. The separator design utilizes a water seal at the outlet which permits the operator to let cold water from the bottom mix with the hot water and boiler steam in the blowdown separator. This reduces outlet temperature to a safe discharge level. These separators require specific plumbing from boiler blowdown valves and require a connection for cold water supply. No electrical hookup is required.